- C1 = danger present. C2 = potentially dangerous. Both make a report unsatisfactory.
- FI = further investigation needed without delay.
- C3 = improvement recommended, but the report can still be satisfactory.
- Landlords must fix C1, C2 and FI items within 28 days or sooner if the report says so.
An Electrical Installation Condition Report (EICR) is a detailed check of the fixed wiring in a property: the consumer unit, circuits, sockets, switches and fittings. At the end, the electrician lists anything they found and gives each item a code. If you have just received a report and are wondering what it all means, this guide is for you.
The four codes at a glance
- C1 – Danger present. There is a real and immediate risk of injury. The electrician should make it safe before they leave, for example by isolating the circuit.
- C2 – Potentially dangerous. Not an immediate danger, but it could become one if a fault occurs. Remedial work is required.
- C3 – Improvement recommended. The installation does not meet the current standard, but it is not considered dangerous. Acting on it would improve safety.
- FI – Further investigation required without delay. The electrician found something that needs more work to understand, such as a circuit they could not trace or test results that need explaining.
Satisfactory or unsatisfactory?
Any C1, C2 or FI code means the overall report is marked unsatisfactory. A report with only C3 observations, or none at all, can be satisfactory.
Common C2 findings in older London homes include missing earthing or bonding to gas and water pipes, sockets without RCD protection that are likely to supply equipment used outdoors, damaged accessories and signs of overheating. Typical C3 items include older consumer units that work safely but lack modern protection.
What landlords must do
Under the Electrical Safety Standards in the Private Rented Sector (England) Regulations 2020, which now also apply to social housing, landlords need an EICR at least every five years. If the report includes C1, C2 or FI items, the landlord must have the remedial or investigative work carried out within 28 days, or sooner if the report gives a shorter deadline.
Once the work is done, the landlord must get written confirmation from a qualified person and give it, along with the report, to the tenant and the local council within 28 days of completion. Councils can issue financial penalties to landlords who do not comply, so it pays to act quickly.
C3 items are not legally required to be fixed, but they are worth budgeting for, especially if they could become a C2 next time.
What homeowners should do
If you own and live in your home, there is no legal deadline, but the codes mean the same thing. Treat C1 and C2 items as urgent, get FI items investigated promptly, and plan C3 improvements when you can. If you are unsure about a finding, ask the electrician to explain it in plain terms and give you a fixed quote for the work.
Booking a check? See our EICR service. Prices start from £140 for a 1–2 bed property, £180 for a 3 bed and £220 for 4+ beds, with full details on our pricing page.
Need a hand? X Electricians are NAPIT-registered and cover North West London 24/7 with no call-out fee. Call 07539 376177 or get in touch online.
This article is general guidance, not legal advice. Always check the latest official guidance for your situation.